Products >> ASPEN Pumps


Standard Peristaltic Pump
no sensor required
Simply connect the Aspen Standard Pump to the approprate drip tray (ising the vinyl tube supplied), mains supply and control link to the air-conditioning units cooling signal. The pump can be mounted remotely as it is self-priming to a height of 2 metres and will pump 6.25 litres of water per hour against a head of 12 metres.

The Aspen Standard pump is designed to run constantly while the air conditioning system is cooling.

This is achieved by linking the pump to the cooling signal. When the cooling switches off, a timer in the pump ensures that the drain tray is emptied before the pump switches off. The signal wire can be connect to the cooling signal and therefore on heating, the pump does not run.

The pump is a peristaltic rotary type - which means that it is quiet in operation, very reliable and will run dry without fear of damage or any embarassing noise. It is not sensitive to water borne contaminants as reciprocating pumps are, and there is no mechanical water sensor to fail!

It is designed to fit in ceiling voids and lift the condensate water from wall mounted machines where a gravity drain is too obstrusive. It can be used on cassettes fitted with an internal life pump. The rollers act as check valves to stop condensate draining back into the drip tray.

The standard pump now has a new push in plug which makes installation and maintenance easier.
TECHNICAL SPECIFICATIONS
- Operates on 240V cooling signal - No loud sound from dry running
- Seft priming lifts 2 metres - Fits into shallow ceiling void
- 12 metres discharge head - Pumps water, fibrously contaminated water and air
- Water flow rate: 6.25 ltrs per hr @
12 metres head
- Pump has a manual test switch
- 3 minute timer overrun - Pump rating: 0.5A, 240V AC
- No siphoning back - Fire retardant plastics
SERVICE GUIDE
Inspect pump head refularly and change the pump head tube every 12 months or more frequently if required.

To remove pump head make sure the roller assembly is vertical. Remove transparent cover and fit replacement pipe. The addition of a smear of silicon grease will ease the refitting of the lid, reducing potential friction noise.

This only takes 3 minutes!

The last switch should always be returned to the NORMAL position after inspection


New plug and socket feature
ELECTRICAL CONNECTIONS
Brown - Permanent/Live
Blue - Neutral
Green/Yellow - Earth
Black - Switched live from signal

INSTALLATION NOTES
This pump is designed to be sitted upright in any position, but at all times it must have free space around the case for ventilation. Ensure there are no kinks or trapped sections in the piping. Vinyl piping must have an ID 1/4" by OD 3/8". Fix the pipes with the tie wraps to the pump outlet and inlet.
A variable connector is provided to make easy installation between the conensate tray outlet and vinyl tube.

 

Send us your feedbackContact us for more info!